STIEBEL ELTRON SOM 10 User Manual

Page 62

Advertising
background image

en

62

Heating / HCs / New HC / Internal

Adjustment channel Description

Adjustment range / selection

Factory setting

HC pump

Heating circuit pump

system dependent

system dependent

Mixer open

Relay selection mixer open

system dependent

system dependent

Mixer closed

Relay selection mixer closed

system dependent

system dependent

Flow sensor

Flow sensor selection

system dependent

system dependent

Sen. outd.

Outdoor sensor selection

system dependent

system dependent

Heating curve

Heating curve

0.3 ... 3.0

1.0

Day correction

Day correction

-5 ... +45 K [-10 ... +90 °Ra]

0 K [0 °Ra]

Tflowmax

Maximum flow temperature

10 ... 100 °C [50 ... 212 °F]

50 °C [122 °F]

Mode

Operation mode

Summer off, Ext. switch, both

Summer off

TSummer

Summer temperature day

0 ... 40 °C [32 ... 104 °F]

20 °C [68 °F]

Daytime on

Daytime on

00:00 ... 23:45

00:00

Daytime off

Daytime off

00:00 ... 23:45

00:00

TSummer

Summer temperature night

0 ... 40 °C [32 ... 104 °F]

14 °C [58 °F]

Ext.switch

External switch sensor input
selection

system dependent

system dependent

Remote control

Remote control option

Yes, No

No

Sen. Rem.control

Remote control sensor input
selection

system dependent

system dependent

Timer

Timer option

Yes, No

No

Mode

Timer mode

Day / Night, Day / Off

Day / Night

Night corr.

Night correction

-20 ... +30 K [-40 ... +60 °Ra]

-5 K [-10 °Ra]

Timer

Timer

-

-

Days of the week

Day selection

All days, Monday ... Sunday,
Continue

-

Timer

Time frame adjustment

00:00 ... 23:45

-

Room therm. 1 ... 5 Room thermostat option (1 ... 5)

Yes, No

No

RTH sen.

RTH sensor input selection

system dependent

system dependent

TRoom.

Room temperature

10 ... 30 °C [50 ... 86 °F]

18 °C [64 °F]

Timer

RTH timer

Yes, No, Inactive

No

Days of the week

Day selection

All days, Monday ... Sunday,
Continue

-

Advertising