Solar external heat exchanger

This function is used to link loading circuits that are
separated by an external heat exchanger.
The allocated relay is energized if one of the selec-
ted stores is being loaded and there is a temperature
difference between the sensor of the corresponding
store and the solar flow.
Any number of the solar stores can be selected.
The relay is switched off if this temperature difference
falls below the adjusted switch-off difference.
In contrast to the bypass function, a differential con-
trol between Sensor HX and the store temperature
can be carried out by means of the heat exchanger
relay.
The reference sensor can be arbitrarily allocated.
In systems in which stores are equipped with their
own loading pumps, the relay “external heat ex-
changer“ controls the primary circuit pump.
The heat exchanger is protected by a non-adjustable
antifreeze function.

Note:
Because of the special hydraulics, the target
temperature option will not work properly
in systems with 2 collector fields.

Adjustment channel Description

Adjustment range / selection Factory setting

Relay

Relay selection

system dependent

system dependent

Min speed

Minimum speed

30 ... 100 %

30 %

Store

Sensor selection

system dependent

1

Sensor HX

Reference sensor ext.HX

system dependent

system dependent

Targ. temp.

Target temperature option

Yes, No

No

Sensor

Target temperature reference
sensor

system dependent

system dependent

Targ. temp.

Target temperature

15 ... 95 °C [60 ... 204 °F]

60 °C [140 °F]

∆Ton

Switch-on temperature difference 1.0 ... 20.0 K [2.0 ... 40.0 °Ra] 10.0 K [20.0 °Ra]

∆Toff

Switch-off temperature difference 0.5 ... 19.5 K [1.0 ... 39.0 °Ra] 5.0 K [10.0 °Ra]

Overrun

Overrun time

1 ... 15 min

2 min

Solar / Opt. functions / Add new function... / Ext. HX