- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (IB) -

3-4 Message Communication

3-44

3

C

om
m

uni

ca

tin

g

w

ith

IB

S

er

ie

s

Group3

0364H

(868)

Laser

emission

stop input

*9

Sets the laser emission stop input status.

Check the emission stop input status of the

operating sensor amplifier from the transmission

stop status (0332H(818)).

The sensor amplifier operates based on OR of

the external input line and cyclic communication.

Parameter range: 0 to 1 (initial value: 0)

0: Emission stop input OFF

1: Emission stop input ON

R/W

DINT

0365H

(869) to

0367H

(871)

(Reserved for system)

0368H

(872)

Sub display's

screen

Sets the sub display's screen.

Parameter range: 0 to 4 (initial value: 0)

0: r.v value

1: Analog value

2: HI setting value

3: LO setting value

4: Zero shift value

R/W

DINT

0369H

(873)

System

parameter

*6

Sets the system parameter.

Reflecting the system parameter setting requires

"system parameter set execution request

(0306H(774)) of the operation command after the

setting is written.

Check the system parameter of the operating

sensor amplifier from 0338(H824).

Bit0:

0:NPN

1:PNP

Bits 1 to 3 (main unit only. The expansion unit is

fixed at 000.)

000: OFF

001: 0 to 5 V

010: 5 to 5 V

011: -1 to 5 V

100: 4 to 20 mA

R/W

DINT

036AH

(874)

Tol. tuning

setting width

Sets the tolerance setting width.

When measurement mode is % mode:

0.00 to 999.99 (initial value: 10.00)

When measurement mode is dimension mode:

0.000 to 99.999 (initial value: 1,000)

R/W

DINT

036BH

(875)

Calibration

function

*10, *11

Sets the correction method.

Parameter range: 0 to 2 (initial value: 0)

0: No correction

1: Measured correction

2: Theoretical correction (% mode only)

R/W

DINT

Class

Attribute

ID

Name

Description

Attribute

Data

Type