2 device maps, Comm u nic a ti ng w it h th e sk-1 000 se ri es, Command response list – KEYENCE DL-CL1 User Manual

Page 38: Remote register rww (master station -> dl-cl1)

Advertising
background image

3-2 Device Maps

3-10

- CC-Link Compatible Network Unit DL-CL1 User’s Manual (SK-1000) -

Comm

u

nic
a

ti

ng

w

it

h th

e

SK-1

000 Se

ri

es

3

Command response list

* This response is provided specifically for data category 10. If the read data has decimal-point position

information and the command is successfully processed, the decimal-point position information is

added to the command response. For details of data category 10, refer to

"Command Parameter

List" (page 3-26).

Remote register RWw (master station -> DL-CL1)

Response

(HEX)

Name

Description

0000

Successfully completed

The command has been processed successfully.

0001

Command number error

The command number is out of range.

0002

Data category error

The data category value is out of range.

0003

ID number out of range

The ID number of sensor amplifier is out of range.

0004

Data number out of range

The data number is out of range.

0005

Write inhibit

Read-only data number. Cannot be written.

0006

Write data out of range

Data written is out of range.

0007

Sensor-to-sensor communication error

An error exists in the communication between sensors.

0008

Motion command access error

Cannot read/write to motion command data numbers.

0009

Motion command data number out of
range

The data number of motion command is out of range.

000A

Motion command execution error

Failed to execute the motion command.

000B

Read inhibit

Write-only data number. Cannot be read.

000C

Operating status error

Command communication (read or write) is
temporarily prohibited because of the operating status
of the sensor amplifier.

FFFF(-1)

Decimal point position of read data*

The command has been processed successfully.
The data being read has one decimal place.
********. *

FFFE(-2)

The command has been processed successfully.
The data being read has two decimal places.
********. **

FFF7(-9)

The command has been processed successfully.
The data being read has nine decimal places.
*. *********

FFF6(-10)

The command has been processed successfully.
The data being read has ten decimal places.
0. **********

Operating

mode

Device no.

(HEX)

Name

Communication

method

Description

Writing range

Sm

al

l-m

e

mo

ry

mo

de
1

Sm

al

l-m

e

mo

ry

mo

de
2

Mo

ni

to

r mo

de
1

RWw[n] + 00

Data category/
command
number

*3

Used when communicating under
handshake control program.
Specifies the data category and
command number of the
parameter to be communicated.

 Upper byte:
00h - FFh
 Lower byte:
00: Read
01: Write
02: Motion
command

RWw[n] + 01

Data number

*3

Used when communicating under
handshake control program.
Specifies the data number of the
parameter to be communicated.

0000h - FFFFh

RWw[n] + 02
to 03

Data to write

*3

Used when communicating under
handshake control program.
Specifies the data to be written in
the parameter to be
communicated.

*4