Data Processing Times

This section describes the length of time taken from detection by a sensor(s) to data
processing by PLC.

Maximum data processing time = (1) + (2) x 2 + (3) + (4)
(1) PLC scan time
(2) Network scan time
(3) Data communication time of DL-CL1
(4) Response time of sensor amplifier

(3) Data communication time of DL-CL1
The lengths of time taken for the data of output or current value to be sent from a
sensor amplifier to the DL-CL1 are summarized below.
Sensor amplifier with calculation function OFF

Number of sensor amplifier units connected

Output, judgment value, or current value

1

9 ms

2

11 ms

3

15 ms

4

17 ms

5

21 ms

6

23 ms

7

27 ms

8

29 ms

CPU unit

CC-Link

master unit

DL-CL1

Sensor amplifier

(1)

(2)

(3)

(4)