5-1 Troubleshooting

5-3

5

Appe

ndi
x

- CC-Link Compatible Network Unit DL-CL1 User’s Manual (SK-1000) -

Communication error indicator (L ERR)

This lamp lights when the DL-CL1 is not communicating properly with the CC-Link
maser station.

Condition

Condition

Corrective action

Not lit

Communicating correctly.

Lighting in red

• The data link is not con-

figured properly.

• The DL-CL1 is config-

ured for Ver. 2 (monitor
mode 2/full mode) while
the master station is con-
figured for Ver. 1.

Check that the data link is properly
configured, and then turn off the
power to the DL-CL1 and back on.

"Configuring the Data Link"

(page 2-10)

Flashing in red
(At regular
intervals)

The setting of the transmis-
sion rate setting switch,
operating mode setting
switch, or station number
setting was changed while
in operation.

If you changed the setting intention-
ally, turn off the power and back on.
The new setting is applied.
If you changed the setting uninten-
tionally, restore the previous setting.
Normal condition is automatically
recovered.

Flashing in red
(At irregular
intervals)

The termination resistor is
not connected correctly.

Connect the termination resistor cor-
rectly. (Normal condition is automati-
cally corrected after the cause is
removed.)

"Connecting the termination

resistor" (page 2-9)

Affected by noise.

Implement noise protection on the
DL-CL1 and CC-Link cable. (Normal
condition is automatically corrected
after the cause is removed.)