Changing the bank number of sensor amplifiers, Changing the bank number of sensor amplifiers -24, 3 communication methods – KEYENCE DL-CL1 User Manual

Page 49: Comm u nic a ti ng w it h th e sk-1 000 se ri es, Set the bank change method to "button

Advertising
background image

3-3 Communication Methods

3-21

3

Comm

u

nic
a

ti

ng

w

it

h th

e

SK-1

000 Se

ri

es

- CC-Link Compatible Network Unit DL-CL1 User’s Manual (SK-1000) -

This example changes the BANK number associated with ID01 and ID02.
(1) Specify a new BANK number in "select BANK number" and execute "request to change BANK" (0 ->

1). In this example, the BANK is changed for both ID01 and ID02 simultaneously.

(2) The "BANK change complete" signal flips from 0 to 1 when the change to the specified BANK

number is completed.

(3) When the "request to change BANK" command is set to 0, the "BANK change complete" parameter

flips to 0.

(4) If an error occurs while changing the BANK for a sensor amplifier of any ID number, the "BANK

change error" signal flips from 0 to 1 (the output is the logical disjunction (OR) for IDs 01 to 04).
Check the value specified in the "select BANK number" parameter.

(5) To clear the BANK change error, set the "clear BANK change error" parameter to 1.

Set the BANK change method to "button."

Changing the BANK Number of Sensor Amplifiers

PLC

Sensor amplifier

Select BANK number 1 (BANK 1)

3 (BANK 3)

RWw04

Request to change BANK of ID 01

RY60

Request to change BANK of ID 02

RY61

Completed in changing BANK of ID 01

RX60

Completed in changing BANK of ID 02

RX61

(4)

BANK change error

RX6F

(5)

Clear BANK change error

RY6F

BANK number of ID 01 1 (BANK 1)

BANK number of ID 02 1 (BANK 1)

3 (BANK 3)

1

1

1

1

1

1

0

0

0

0

0

0

(3)

(1)

(2)

Point