System specifications, Environmental specifications, System configurations / appliances – Potter PFC-6075R User Manual

Page 10

Advertising
background image

2-4

PFC-6075R • 5403594 • REV D • 9/14

Section 2: Before You Start Installation

This section addresses information that will help you in completing a successful installation, such as the PFC-6075R cabinet

layout, specifications, environmental considerations, and calculating the battery circuit and SLC current draw requirements.

System Specifications

Cabinet Description

y

y

Sixteen (16) gauge sheet steel with hinged, removable locked door

y

y

Enclosure dimensions – 16" x 17" x 3-7/8"

Visual Indicators

y

y

LCD (2 x 16 alphanumeric character display)

y

y

LED indicators (Red, Green, Amber)

LCD Description

y

y

Alarm, Supervisory and Trouble conditions display applicable condition, status and circuit for each correlating condition

Environmental Specifications

y

y

Mount indoors only.

y

y

Temperature 32° to 120°F, humidity 93% non-condensing.

y

y

Verify panel is properly grounded.

y

y

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make

all cable entries from the sides, bottom, or rear of the cabinet. Verify that they will not interfere with the batteries or other

components.

y

y

The panel and system must be tested and maintained in accordance with all local and national codes and ordinances.

System Configurations / Appliances

Table 2: System Configurations / Appliances

Model

Description

Local

Releasing

Service

Auxiliary

Remote

Station

Central

Station

Proprietary

PFC-6075R

Main Board/Panel Assembly

Y

Y

Y

Y

Y

Y

CA-6075

Class A Expander

O

O

O

O

O

O

UD-1000

DACT

N

N

N

Y

Y

Y

RA-6500R / RA-6500

or RA-6075R / RA-6075

LCD type remote Annunciator

O

O

O

O

O

O

PSN-1000 or

PSN-1000(E)

Intelligent Power Supply Expander

O

O

O

O

O

O

LED-16

LED Annunciator

O

O

O

O

O

O

DRV-50

LED Driver

O

O

O

O

O

O

RLY-5

Relay Expander

O

O

O

O

O

O

FCB-1000

Fire Communications Bridge

O

O

O

O

O

O

FIB-1000

Fiber Interface Bridge

O

O

O

O

O

O

SPG-1000

Serial/Parallel Gateway

O

O

O

O

O

O

3005013

End of line resistor assembly

Y

Y

Y

Y

Y

Y

3005012

End of line resistor and diode

N

Y

Y

N

N

N

Y = Yes, required for applicable section

N = No, not required for applicable section

O = Optional, may or may not be used, has no affect on the applicable section.

Advertising