5-48

PFC-6075R • 5403594 • REV D • 9/14

Table 9: Programming Options

Topic

Feature or

Option

Permitted

in UL (Y/N)

Possible Settings

Setting(s) Permitted

in UL864?

Comment

Zone

Zone Type

Y

Alarm

Supervisory

Positive Alarm Sequence

Auxiliary

Releasing

Fire Drill

System Alarm

System Supervisory

System Trouble

All settings allowed

Zone

Alarm Count

Y

1-10

All settings allowed

Zone

Silenceable

Y

Yes/No

All settings allowed

Zone

Silence Inhibit

Y

Yes/No

All settings allowed

Zone

Auto Silence

Y

Yes/No

All settings allowed

Zone

Auto Unsilence

Y

Yes/No

All settings allowed

Zone

Restore Delay

Y

0-300 Sec

Full range allowed

Zone

Latching

Y

Yes/No

All settings allowed

Zone

Local

Y

Yes/No

All settings allowed

Zone

Output Pattern

Y

Constant

ANSI Temporal

March Code

Double Time

All settings allowed

Zone

Day Sensitivity

Y

1.1%-3.5%

Full range allowed

Within listed range

of sensor

Zone

Night Sensitivity

Y

1.1%-3.5%

Full range allowed

Within listed range

of sensor

Zone

Fixed Heat

Setting

Y

135

̊

F-185

̊

F

Full range allowed

Within listed range

of sensor

Zone

Combo ROR/

Fixed Setting

Y

135

̊

F-174

̊

F

All settings allowed

Within listed range

of sensor

Releasing

Abort Type

Y

ULI, IRI, AHJ, NYC

ULI

Only ULI is permitted in

UL installations

Releasing

Pre-Release

Timer

Y

0-60 Sec

Full range allowed

Length of time of

pre-release

Releasing

Pre-Release

Pattern

Y

Constant

ANSI Temporal

March Code

Double Time

All settings allowed

Pattern from NAC

during Pre-Release

Releasing

Manual Release

Timer

Y

0-30 Sec

Full range allowed

Length of time of

Pre-Release

Releasing

Manual Release

Abort Allowed

Y

Yes/No

All settings allowed

Specifies whether Man-

Release is Cancellable

Releasing

Soak Time

Y

0-20 Minutes

Full range allowed

Length of time the

release circuit is active

post release