Potter PFC-6075R User Manual

Page 108

Advertising
background image

6-102

PFC-6075R • 5403594 • REV D • 9/14

Section 6: PSN-1000 / PSN-1000(E) – Installing, Operating & Programming

The PSN-1000 and PSN-1000(E) power supply boards provide power and communication expansion capability to the

PFC-6000 series control panels. They provide an electrically isolated P-Link repeater output that supports additional power

and communications distance. The PSN-1000(E)'s larger cabinet allows space for mounting up to six (6) additional P-Link and

expansion cards (i.e., FIB-1000, etc.).

Board Specifications

Cabinet Descriptions

y

y

Sixteen (16) gauge sheet steel with hinged, locked doors

y

y

Enclosure dimensions

PSN-1000 – 16" x 17" x 3-7/8" (non-removable door)

PSN-1000(E) – 26" x 17.6" x 3.75" (removable door)

Visual Indicators

y

y

LED indicators (Green & Amber)

Environmental Specifications

y

y

Mount indoors only.

y

y

Temperature 32° to 120°F, humidity 93% non-condensing.

y

y

Verify panel is properly grounded.

y

y

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make

all cable entries from the sides, bottom, or rear of the cabinet. Verify that they will not interfere with the batteries or other

components.

y

y

The panel must be tested and maintained in accordance with all local and national codes and ordinances. Refer to

Appendix D: PSN-1000/PSN-1000(E) Maintenance and Testing for information on maintenance and testing

recommendations.

Electrical Specifications

Please refer to the table below for the board's electrical specifications:

Table 22: PSN-1000/PSN-1000(E) Board Electrical Specifications

# NACs

Rating per NAC

Input Circuits

Style and Class

6

3 Amp

1 Amp

Class A or B

NACs are Power Limited

Note: Refer to the "NACs Wiring" topic located in

this section for Class A wiring requirements.

Wiring Specifications

There are several wiring requirements to consider before connecting circuits to the PSN-1000/PSN-1000(E) board:

1) the circuit separation, and 2) the wiring types.

Circuit Separation

y

y

Separations between the different wiring types must be maintained by at least ¼ inch and the wire insulation must be for the

higher voltage.

y

y

The two cabinets have various conduit knockouts located for ease of wire installation and allowing the installer to maintain

power limited and non-power limited connections.

Advertising