Signaling line circuit (slc) installation, Signaling, Signaling listed l u – Potter PFC-6075R User Manual

Page 21

Advertising
background image

3-15

PFC-6075R • 5403594 • REV D • 9/14

Section 3: Installation

This section addresses installation procedures for SLCs, NACs and optional modules, including the DACT (UD-1000),

Class A Card, and Remote Annunciators. Wiring requirements and configuration examples are included throughout this section.

Instructions for addressing SLC devices which must be completed before programming your system are also included. Please

read this section carefully before installing devices and/or modules to insure proper installation.

Note: Instructions for installing the PSN-1000/PSN-1000(E) and/or the IP Dialer accessories are located in

Sections 6 and 7, respectively.

Signaling Line Circuit (SLC) Installation

The SLC panel provides power and communication to each of the sensors and modules connected. The SLC is polled by the

system every 4–5 seconds. This panel has a loop capacity of 75 addressable points, which may be configured in any combination

of smoke sensors, heat detectors, and input or output modules.

SLC Wiring Requirements
The wiring parameters listed below MUST be followed to ensure proper installation:

•y

Maximum wiring resistance between two (2) Short Circuit Isolators (SCIs) must be less than 10 ohms.

•y

Total resistance must be below 50 ohms.

•y

Maximum wire resistance must be calculated based on 0.1 ohm per SCI.

•y

Maximum loop capacitance must be 0.5 micro farads.

•y

All SLC wiring is low voltage and power limited.

Class B, Style 4 Wiring Configuration

Figure 7. Example of SLC Wiring - Class B, Style 4

S- S+ C

NO

(NC)

Potter Electric Signal Company

Miniature Contact Module

Model No. MCM

Ser. No. xxxxxx

Document:

TN51314e date: XX.XX.2009

WARNING:

All Terminals are power limited

Address No.

SIGNALING

LISTED

L

U

FIRE ALARM EQUIPMENT

XXXX

Address No.

Potter Electric Signal Company

FIRE ALARM EQUIP

MENT

XXXX

24- 24+ S- S+

B- B+ A- A+

Conventional Initiating Zone Module

Model No. CIZM-4

Ser. No. xxxxxx

Document: TN51313e date:XX.XX.2009

Compatibility Identifier: INTE01
WARNING :

Power supply for terminals 24+ and 24- must

be power limited

All Terminals are power limited.

SIGNALING

LISTED

L

U

PFC-6000

Series

SLC Loop (Class B)

Terminal Connections

3

6

7

8

5.1kΩ

5.1kΩ

DWG # 593-7A

All devices require an address prior to connecting to the

control panel. Refer to “Addressing SLC Devices” located

later in this section for details.