Relay board installation (rly-5) – Potter PFC-6075R User Manual

Page 42

Advertising
background image

3-36

PFC-6075R • 5403594 • REV D • 9/14

Setting Addresses
The DRV-50's address is set by dip switch S1, which is located on the back of the board. The address must be set in the range of

one to thirty-one (1–31) to be recognized by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP

switch programming.)

Figure 42. DRV-50's Back Panel View Showing Dip Switch Location

Relay Board Installation (RLY-5)

The panel may be equipped with thirty-one (31) RLY-5 (Relay Board) modules. Each RLY-5 provides 5 programmable output

relays, which can be individually mapped to any zone. The RLY-5 is controlled over the 4-wire P-Link connection. The RLY-5

mounts in a mounting bracket as shown below, and then installed into the panel cabinet, or in either of the AE-8 or AE-14 accessory

cabinets.

Figure 43. RLY-5 Board Showing Mounting Bracket

The RLY-5 higher current required for the relay outputs can be provided by the panel, or from an auxiliary power source as shown
below. The auxiliary power can be any 24VDC source, and is fully supervised.

Figure 44. RLY-5 Wiring to Control Panel or Auxiliary Power Supply Examples & RLY-5 Showing Normally Open / Normally Closed Contacts

DWG #608-10

DWG #608-22

Dip Switch

P-Link

Connections

S1

RLY PWR P -Link

-

+ -

+ A B

P-Link from

control panel

Example:

Powered by

control panel

-Link

-

+ -

+ A B

P-Link from

control panel

Example:

Powered by

aux supply

Power from

auxiliary

supply

RLY PWR P

NC (Normally Closed)

C (Common)

NO (Normally Open)

NC C NO

RELAY 1

NC C NO

RELAY 2

NC C NO

RELAY 3

NC C NO

RELAY 4

NC C NO

RELAY 5

DWG #608-10C

DWG #608-8