Mapping Terminology
The table below provides mapping terms that may be helpful to you in understanding the mapping concept:

Table 15: Mapping Terminology

Term

Definition

Mapping

Creating relationships between devices, modules and sensors and defining their behavior.

Zone

A group of devices.

y

y

Zones may represent a group of devices located in a specific physical area at the site.
Example: Zone 1 comprised of all devices located in the main lobby of a hotel, [i.e., pull station #1,

one (1) sounder base, and one (1) strobe-NAC].

y

y

Zones may represent a set of devices configured for a specific function; their location may be

scattered throughout the site. This group is a “logical” grouping or zone.
Example: Zone 2 comprised of all devices in Zone 1 as described above, plus a 2

nd

pull station

located at end of a hallway and two (2) additional Sounder bases.

Notes:

1. If all input / output devices are grouped into one (1) zone, when any input is activated, all outputs

activate.

2. A device or point may be mapped into more than one (1) zone.

Point

Any specific device, module or appliance connected to panel.

Latching

Device will not automatically reset; device must be RESET at the keypad to remove condition.

Non-Latching

Device will automatically reset when condition is no longer present, i.e., smoke detector resets once

condition clears.

Cross Zoning

The purpose of creating cross zones is to ensure that two (2) or more separate zones are activated before

an output zone is triggered.
Example: Smoke detector in Zone 1 (R&D Lab), and a heat detector in Zone 2 (Main entrance) are

activated, triggers an air handler circuit.

y

y

The redundancy in this example provides verification of an alarm condition by requiring that both

sensors in two (2) different zones are activated before an output occurs.

y

y

There are no limits to the number of cross zones that can be mapped to the same output; as soon as a

pair of input devices detects an “alarm” condition, the output will be activated.

Zone Types / Styles
You may define or configure each zone to serve a specific purpose or to create specific output results. For procedures on how to

select Zone styles, refer to the “Configuring Zones” section of this manual. The following zone styles are available:

Table 16: Zone Styles

Zone

Description

Alarm

•y

Default zone type.

•y

Sets system into an Alarm condition when any input is activated.

Supervisory

Used for all Supervisory inputs.

Positive Alarm Sequence

Implements Positive Alarm Sequence.

Auxiliary

Used for all “Aux” inputs.

Releasing

Dedicated to handling release sequence.

Fire Drill

Comprised of input / output devices that will activate when running a Fire Drill.