Led annunciators installation (led-16) – Potter PFC-6075R User Manual

Page 39

Advertising
background image

3-33

PFC-6075R • 5403594 • REV D • 9/14

Remote Annunciators Installation (RA-6500R / RA-6500 and RA-6075R / RA-6075)

The panel supports up to thirty-one (31) annunciators in any combination may be connected to the main fire control panel. The

RA-6500R/RA-6500 provides a 4 x 40 character LCD display. Whereas, the RA-6075R/RA-6075 provides a 2 x 16 character

LCD display, along with standard function and numeric keys. All annunciator models listed are designed to be mounted on a flat

non-condensing surface or electrical box.

Setting Addresses
An annunciator's address is set by dip switch S1, which is located on the back of the annunciator. The address must be set in

the range of one to thirty-one (1–31) to be recognized by the panel. (Refer to chart on the previous page for P-Link DIP switch

programming.)

Figure 34. Annunciator Back Panel View

LED Annunciators Installation (LED-16)

The panel supports up to ten (10) LED-16 annunciators, which display alarm, supervisory, and trouble conditions for up to

16 zones per LED-16. It also provides Silence and Reset functionality. Blank zone labels are provided for use with the LED

annunciator to label each zone name or identifier. The labels may be typed or written on the supplied card-stock, and then inserted

into the back of the front panel as shown in the right-most figure below.

Note: This panel supports up to ten (10) LED-16 annunciators and/or DRV-50 drivers in any combination.

Figure 35. LED-16 Module & Board

DWG #608-4

DWG #608-5

Zone labels

will display here

Labels are inserted

here as needed

DIP SWITCH

A

B

+

-

DWG #593-31

S1

P-Link

Connections