I1 i2 i 3 i 4 – Potter PFC-6075R User Manual

Page 41

Advertising
background image

3-35

PFC-6075R • 5403594 • REV D • 9/14

The 50 programmable LED outputs are located on connectors P1-P5, each containing ten (10) LED outputs and two (2) 5VDC

outputs. The system LEDs and PZT control outputs are located on connector P6. LEDs are wired as shown below; no external
resistor is required. All outputs are power limited.

Figure 39. DRV-50 "P1-P5" and "P6" Connectors

Note: All connections to P1-P6 are limited to same room installations.

The 4 programmable dry-contact inputs are located on connector P7. All input circuits are power limited and use a 5.1k

EOL resistor. The inputs can be programmed for any of the contact input functions available for other input circuits available

on the panel. Inputs I1-I4 are Class B dry contact inputs only. All contact inputs are fully supervised, and ground fault detection

impedance is 0 ohms.

Figure 40. DRV-50 "P7" Dry-Contact Inputs

Note: All contact inputs are fully supervised. Ground fault protection impedance is 0 ohms.

The higher current required for the LED outputs can be provided by the panel, or from an auxiliary power source as shown below.

The auxiliary power can be any 24VDC source, and is fully supervised.

Figure 41. Examples of Wiring DRV-50 from Control Panel or Auxiliary Power Supply

TRB

SUP

ALR

SIL

EARTH

PWR

PZT-

LED+

LED1

LED10

LED+

LED+

Programmable LED

Connectors P1-P5

System LED and PZT

Connector P6

DWG #608-8

LED PWR P -Link

-

+ -

+ A B

P-Link from

control panel

Example:

Powered by

control panel

LED PWR P -Link

-

+ -

+ A B

P-Link from

control panel

Example:

Powered by

aux supply

Power from

auxiliary

supply

DWG #608-6

Dry Contact Inputs (P7)

I1

I2

I

3

I

4

5.1k

5.1k

5.1k

5.1k

P7

DWG #608-9

Max. wiring resistance = 100 ohm
Max. wiring capacitance = 1 uF
Max. wiring length = 10,000 ft.
Max. IDC voltage = 24 VDC
Max. IDC current = 5 mA

Advertising