Appendix A: Basic Operating Instructions

These instructions must be framed and displayed next to the PFC-6075R panel in accordance with NFPA 72 fire code for Local

Protected Fire Alarm Systems. Test the system in accordance to NFPA 72.

Table 25: Button Functions

Button

Function

ACK

Arrows

Drill

Esc

Reset

Silence

Table 26: Operating Instructions

Operation

Task

Silence Alarms, Troubles

Press the SILENCE pushbutton.

Acknowledge Alarms,

Troubles

Press the ACK pushbutton.

Reset Alarms

Press the RESET pushbutton.

View Alarms, Troubles

Press arrows to view alarms / troubles.

Conduct a Fire Drill

Press the DRILL pushbutton; press the RESET button to exit Drill mode.

View Point’s Status

•y

Press ENTER to display the Main Menu.

•y

Press 5System Tools; enter panel’s code.

•y

Press 2 Point Control.

•y

Scroll Up/Down to choose Internal SLC / PWR, and press ENTER.

•y

Enter Addr / Ckt No. and press ENTER.

•y

Press Up/Down to view previous / next points.

Check Detector Sensitivity

•y

Press ENTER to display the Main Menu.

•y

Press 5System Tools; enter panel’s code.

•y

Press 1SLC Tools.

•y

Press 1SLC Pinpoint.

•y

Enter Addr #, press ENTER; detector address and type displays.

•y

Press ENTER to display current usage.

•y

Press Up to display Day/Night Sensitivity settings.

•y

Press Up / Down to scroll through point’s day / night sensitivity settings.