FIB-1000 Wiring
FIB-1000s are installed in pairs. (Please refer to Diagrams #1 & 2 shown below to properly wire the two FIB-1000s.) The first

FIB-1000, referred to as "FIB-1000 (A)" below can be installed in any of the compatible fire alarm enclosures, or the FIB-

1000RM. It is connected via the 4-wire P-Link connection. Set S2 on FIB-1000 (A) to the "OFF" position, which provides an

outgoing fiber option connection. That fiber optic connection can be connected as Class A or Class B to the second FIB-1000,

referred to as "FIB-1000 (B)" below.

The second FIB-1000 (B) is installed in a PSN-1000E (shown in Diagram #2 below). Set S2 on FIB-1000 (B) to the "ON"

position. It then provides an outgoing P-Link connection. Connect the 4-wire P-Link on the FIB-1000 (B) to the P-Link

connection on the PSN-1000E.

To power the FIB-1000 (B), connect the 24VDC "+" and "-" terminals on PSN-1000E (shown in Diagram #2 below) to the

isolated P -Link 24 VDC "+" and "-" terminals. The PSN-1000E's isolated P-Link can now be used to connect any other

P-Link appliance, including the RA-1000, LED-16, and PSN-1000/PSN-1000E.

Figure 50. Diagram #1: FIB-1000 Wiring Diagram Showing Detail

Figure 51. Diagram #2: FIB-1000 Wiring Diagram Shown Installed in PSN-1000E Cabinet

Master Panel or PSN1000E

P-LINK

PSN-1000

B

A

+

-

B

A

+

-

To Additional

P-Link Devices

B

A

+

-

S1

S2

ON

OFF

-

+
A

B

S2

S1

ON

OFF

FIB-1000 (A)

Upstream FIB

S2 = OFF

S2 =

OFF

FIB-1000 (B)

Downstream FIB

S2 = ON

ON

R x 2

T x 2

R x 1

T x 1

T x 1

R x 1

T x 2

R x 2

Fiber Optic

Cable

OUT

IN

DWG #608-25B

PSN-1000E

B

A

+

-

B

A

+

-

T1

R1

R2 T2

B

A

+

-

FIB-1000 (B)

To Additional

P-Link Devices

Fiber In

DWG #608-25A

Advertising