5-78

PFC-6075R • 5403594 • REV D • 9/14

Table 16: Zone Styles

Zone

Description

System Alarm

Used for outputs that will be activated upon any alarm.

System Supervisory

Used for outputs that will be activated upon any supervisory.

System Trouble

Used for outputs that will be activated upon any trouble.

Zone Attributes
Zone attributes are the settings that control the overall behavior of devices within the zone. The zone may be configured as

latching or non-latching, silenceable vs. non-silenceable, among other attributes

Tips: Double-click in a field to modify an applicable field, i.e., zone name or alarm count. Click in fields with a

selection box to select or deselect the option, i.e., silenceable or latching.

All zones default to an “Alarm” style or type when first created. The figures shown below are examples of the default attributes of

a "Releasing" zone.

Figure 103. Example of Zone Attributes (Fields 1-10)

Figure 104. Example of Zone Attributes (Fields 11-20)

Refer to the table below for a brief explanation of zone attributes:

Table 17: Zone Attributes

Attribute

Description

Zone Name
Default = Zone “x”

(where “x” is a sequential number)

•y

Zone name may be up to sixteen (16) alphanumeric characters.

Alarm Count
Default = 1

•y

Defines the number of inputs that must be in alarm before outputs are

activated.

•y

Default is one (1); up to 10 inputs may be selected.

Silenceable / Non-Silenceable
Default = Silenceable

•y

If zone defined as “silenceable” allows an operator to silence outputs by

pressing the SILENCE button.

Latching / Non-Latching
Default = Latching

•y

Available for one (1) count zones only.

•y

Latching zone requires operator to press Reset.

•y

Non-latching zone will automatically turn off outputs when condition clears.

Local / Non-Local
Default = Non-Local

•y

Used only for “Report by Zone” option.

•y

Allows a zone to be specified as a non-reporting zone.