Municipal box connection, Relay outputs – Potter PFC-6075R User Manual

Page 118

Advertising
background image

6-112

PFC-6075R • 5403594 • REV D • 9/14

Municipal Box Connection

When the PSN-1000/PSN-1000(E) is programmed as a municipal box connection, the circuit is power limited and supervised for

open and short circuit conditions. It also provides a local energy connection. Please refer to the figure shown below for a wiring

example.

Configuration Characteristics

y

y

NAC1-NAC6's trip current is 3 amps.

y

y

Maximum voltage rating is 24 VDC.

Notes:

1. The panel has ground fault detection on municipal box connection circuits.

2. The impedance to ground for ground fault detection is 0 ohms.

Figure 156. PSN-1000 Configured as Municipal Box

-

I1 + - NAC 1 + - NAC 5 + - NAC 3 +

-

+ A B

-

I2 + - NAC 2 + - NAC 4 + - NAC 6 +

-

+ A B

P-LINK

Notes:

The EOL device shall be installed in the same electrical

enclosure as the Municipal Box.

Municipal

Box

+

-

End of line device

5.1k ohm 1/2W

Part #3005012

Relay Outputs

The board has two (2) relay outputs: a dedicated Trouble relay and a Low AC relay. The dedicated Trouble relay is a failsafe

trouble relay that changes position anytime a trouble condition occurs.

The relays have a contact rating is 24VDC / 3.0A, 125VAC / 3A, and a Power Factor of 1.0. These outputs are non-power limited

and are not supervised.

Note: If the power supply is power-limited, then the outputs are power limited.

Figure 157. PSN-1000's Relay Outputs

LOW AC

NC COM NO

TROUBLE

NC COM NO

DWG #602-31

DWG #602-32