Potter PFC-6075R User Manual

Page 25

Advertising
background image

3-19

PFC-6075R • 5403594 • REV D • 9/14

When configuring a Class B, the DCM-4 has two (2) addresses. If address No.1 is set, input circuit No.1 (NO1, C1) will be

addressed as No.1, and input circuit No.2 (NO2, C2) will automatically be addressed as No.2. Refer to the figure below for an

example of wiring a Class B DCM-4.

Figure 16. DCM-4 with Two Class B Circuits

S-

S+

SLC Loop

To Next Module

From FACP or Previous Module

Dual Contact Module

Model No. DCM-4

LED

Note: The resistance of external wiring shall be less that 100Ω.

The capacitance of external wiring shall be less than 1 micro farads.

JP1

Select Style 4

NO1

C1

Z1

NO2

C2

Z2

Address #

Address #+1

DWG #593-16

Twin Relay Module – 4 inch mount (TRM-4)
The TRM-4 has two (2) contacts that are active simultaneously when TRM-4 is in the active mode. Normal output is nonpower-

limited, unless the power supply connected to the TRM-4 is power-limited and the circuits are power-limited.

Figure 17. Example of TRM-4 Wiring

S-

S+

SLC Loop

To Next Module

From FACP or Previous Module

Twin Relay Module

Model No. TRM-4

LED

NO1

C1

NC1

NO2

C2

NC2

Contact Rating:

24VDC / 2.0A

125VAC / .5A

Normally Open 1

Common 1
Normally Closed 1

Normally Open 2

Common 2
Normally Closed 2

DWG. #593-17

Monitored Output Module – 4 inch mount (MOM-4)
If the power supply connected to the MOM-4 is power limited, then the outputs are power limited. The MOM-4 module may be

wired as a releasing device. Examples of a MOM-4 wired as a conventional and a releasing application are provided here.

Figure 18. Example of MOM-4 with NAC Connections

Monitored Output Module

Model No. MOM-4

From FACP or Previous Module

To Next Module

From FACP or Previous Module

To Next Module

24-

24+

S-

S+

A-

A+

SLC Loop

LED

JP1

Select DC

Notification Appliance

5.1KΩ 1/2W EOLR

_

+

_

+

_

+

Output Rating:

24VDC / 2.0A

DWG #593-18