Potter PFC-6075R User Manual

Page 100

Advertising
background image

5-94

PFC-6075R • 5403594 • REV D • 9/14

Programming Modules

This section addresses how to program optional all P-Link appliances, including the DACT (UD-1000), RA-6500R, RA-6075R,

CA-6075 Class A expansion card, LED-16 annunciators, and others.

CA-6075 Class A Converter Module
The PFC-6075R supports one (1) Class A Expander card.

To add and configure a Class A module:
1. Select the Class A Card function from the system panel.
2. Click the Add Device button. The “Add Device” window displays.

Figure 131. CA-6075 Class A – Add Device Window

Note: If you attempt to add more than one (1) Class A card, an error dialog box displays, as shown below:

Figure 132. Unable to Add Dialog Box

3. Double-click in the “SLC Class” field to select class type (A or B).

4. Double-click in the “P-Link Class” field to select class type (A or B).