PFC-6075R • 5403594 • REV D • 9/14

SLC Functions
The SLC configuration options are described in the table below:

Table 20: SLC Configuration Functions

Function

Description

Unused

SLC point is unused.

Addr Detector Photo

Photoelectric Sensor (PSA)

Addr Detector Photo Heat

Combination Photo-Heat Sensor (PSHA)

Addr Detector Heat Fixed

Fixed Temperature Heat Detector (FHA)

Addr Detector Heat Combo

Combination Fixed Temperature and Rate-of-Rise Heat Detector (RHA)

Addr Relay General Purpose

Addressable Relay Module (TRM)

Addr NAC General Purpose

Monitored Output Module (MOM)

Addr Zone Module

Two-Wire Conventional Detector Module (CIZM)

Addr Sounder Base

Addressable Sounder Base (ASB)

Addr Relay Base

Addressable Relay Base (ARB)

Contact Input Pull Station

Dry contact input options used with MCM, SCM or DCM modules; available

for on-board I/O circuits.

Note: When using an input module on an abort function, there is a 6-second

delay before panel responds.

Contact Input Water Flow
Contact Input Supervisory
Contact Input Tamper
Contact Input Fire Drill
Contact Input Trouble Monitor
Contact Input Aux
Contact Input Abort (see note)
Contact Input Reset
Contact Input Silence

Contact Input Disable Inputs

Contact Input Disable Outputs

Contact Input Disable Inputs/Outputs