Section 1: Introduction

The Model PFC-6075R is a listed and approved, microprocessor based addressable fire control panel and complies with UL-864,

NFPA-12, NFPA-12A, NFPA-13, NFPA-15, NFPA-16, NFPA-17, NFPA-17A, NFPA-72, NFPA-750, NFPA-2001, CSFM, and

NYC Fire Department Certificate of Approval #6157.
The PFC-6075R system software is compatible with Windows XP, Windows Vista and Windows 7 Operating Systems;

additionally, the latest version of Microsoft .NET Framework is required. The system software incorporates conventional

shortcuts, and provides great flexibility in effectively programming individual or groups of devices. The operational mode

behavior of the four (4) on-board circuits (NACs 1 and 2, and Input/Outputs 1 and 2) can be customized.

This flexibility enables

configuration of system points to maximize protection throughout controlled site(s).

Purpose of This Manual

This manual is intended to assist in the installation and programming the PFC-6075R Fire Alarm Control Panel. Refer to this

manual to properly install and program the PFC-6075R. It is recommended that the user follows the procedures as outlined in

this manual to assist in proper installation and prevent damage to the control panel and associated equipment.

System Overview

The PFC-6075R system is designed for use as a fire control panel for life safety applications, as a releasing panel for pre-action

and deluge, water-based extinguishing systems or for agent extinguishing systems. It may also be used as a stand-alone fire

control panel.

System Features

y

y

The PFC-6075R features a built in signaling line circuit (SLC), and is capable of supporting 75 Potter/Nohmi protocol

devices.

y

y

5.0 Amp 24vdc Power Supply

y

y

Two (2) Notification Appliance Circuits (NACs) each rated at 3.0 Amps maximum.

y

Power Limited

y

Built in Sync

y

Cadence Patterns

y

Auxiliary Power

y

Releasing Solenoid Output

y

y

Two (2) Input/Output Circuits each rated at 1.0 Amps maximum.

y

Power Limited

y

Built in Sync

y

Cadence Patterns

y

Auxiliary Power

y

Contact Input

y

Reverse Polarity Driver

y

Releasing Solenoid Output

y

y

Support for all major synchronization patterns.

y

Potter

y

Gentex®

y

CooperWheelock®

y

System Sensor®

y

y

Built-in Ethernet port for programming and network connectivity.

y

y

Built-in e-mail support to communicate system status and event information.

y

y

Customizable Reminder E-mails.

y

y

P-Link RS-485 bus supports system accessories.

y

y

1,000 event non-volatile history buffer.

y

y

Learn mode enrolls connected sensors and modules for efficient system programming.