Scenario 2: Class B Loop – Isolated Branch Configuration
In this configuration, there are 4 separate branches each with an isolation device / module and 1 or more sensors. Each sensor

requires an address, as shown in Scenario #1 (isolators do not require an address). However, in this scenario, each isolator

consumes power equal to 8 devices. To calculate the total device load, refer to the following rule:

Device Load Rule for Branch Configurations
Count all devices, including isolators, on the branch.

• If the count is <=8, allocate 8 as the device load.

• If the count is >8, allocate the actual device count number.

Figure 4. Example of a Class B Loop – Isolated Branches

Configuration Summary:
Branch #1 has 3 devices = 8 power allocations

Branch #2 has 2 devices = 8 power allocations

Branch #3 has 10 devices = 10 power allocations

Branch #4 has 4 devices = 8 power allocations

Total addressable devices = 15 (sensors only) out of 75 addressable points.
Total device load = 34 out of a possible 127 power unit allocations.

LEGEND:

ISO Module/

Device

Sensor

BRANCH #1

BRANCH #2

BRANCH #3

BRANCH #4

PANEL

Total devices = 3

Total devices = 2

Total devices = 10

Total devices = 4

DWG #593-3