PFC-6075R • 5403594 • REV D • 9/14

Setting Addresses

A SPG-1000 address is set by dip switch S1. The address must be set in the range of one (1) to thirty-one (1–31) to be recognized

by the panel. (Refer to the "P-Link Addresses" table shown earlier in this section for DIP switch programming.)

Figure 55. SPG-1000 Back Panel View Showing Dip Switch Location

DACT Installation

Phone lines are high voltage and should be run in a separate conduit from other circuits. The wire conductors connecting the

DACT to the phone system should be 26 AWG or larger.

The UD-1000 Digital Alarm Communicator Transmitter provides connections for two (2) phone lines for communication to a

monitoring station. The UD-1000 DACT communicates using the SIA-DCS or Ademco Contact ID protocols. Only one UD-1000

is allowed per main control panel, for convenience the UD-1000 is typically programmed as device ID #01.

The UD-1000 must be installed prior to any other telephone equipment in the building to ensure proper operation. An RJ31X

jack can be installed to provide the connection to the telephone lines, a patch cable between the RJ31X jack and the built in

RJ-11 jacks on the UD-1000 provide a convenient connection method. The UD-1000 automatically monitors each phone line for

voltage and has the ability to seize the line and connect with a remote receiver. Once the communication is complete, the DACT

will hang up the phone line.

The DACT is provided with an RJ-11 jack for each phone line. In order for the DACT to work properly, it must be installed on

a plain old telephone service (POTS) or equivalent as deemed by the authority having jurisdiction. The DACT must be installed

before any other equipment to ensure it can seize the line and disconnect any other lines.

P-Link

Connections

Dip Switches

DWG #608-25