Toa NX-100S Installation User Manual

Page 110

Advertising
background image

6-7

Chapter 6: APPENDIX

[Operations caused by a change in the contact input and output devices' power statuses]

Contact input
device

Contact input ON

ON

Contact output ON

OFF

Contact output
device

ON

ON

Power OFF

Power ON

Power OFF

Power ON

Network

(Output turns OFF when
power is switched OFF.)

(Receives contact ON
information.)

(Transmits initial status
information when power
is switched ON.)

1.8.5. Simultaneous control of multiple contact outputs

Simultaneously providing the contact bridge to multiple outputs in the same device may result in control failure
(see charts below).
This can be avoided by shifting each control timing by 100 ms or more at the contact input side. Note that if
control fails, retry operation is automatically performed.

Contact input device

ON

ON

ON

Contact output device

ON

ON

Possible failure to turn ON

ON

Simultaneously
timed controls

Simultaneously
timed controls

Simultaneously
timed controls

Simultaneously
timed controls

ON

Possible failure to turn ON

Contact input device

ON

ON

ON

Contact output device

ON

ON

Possible failure to turn ON

ON

ON

Possible failure to turn ON