Calibration
• 97
Analog Input Module‘s Calibration Voltages
Table 5-1: ND-6011/D/ND-6018 Calibration voltages
Code Input
Range
Offset Calibration
voltage
Span Calibration
Voltage
00
±15 mV
0 mV
+15 mV
01
±50 mV
0 mV
+50 mV
02
±100 mV
0 mV
+100 mV
03
±500 mV
0 mV
+500 mV
04
±1 V
0 V
+1 V
05
±2.5 V
0 V
+2.5 V
06
±20 mA
0 mA
+20 mA
0E
J (0
°C to 760°C)
0 mV
+50 mV
0F
K (0
°C to 1000°C)
0 mV
+55 mV
10
T (-100
°C to 400°C)
0 mV
+30 mV
11
E (0
°C to 1000°C)
0 mV
+78 mV
12
R (500
°C to 1750°C)
0 mV
+25 mV
13
S (500
°C to 1750°C)
0 mV
+19.5 mV
14
B (500
°C to 1800°C)
0 mV
+15 mV
15
N (-270
°C to 1300°C)
0 mV
+55 mV
16
C (0
°C to 2320°C)
0 mV
+39 mV
Table 5-1: ND-6012/D/ND-6017 Calibration voltages
Code Input
Range
Offset Calibration
voltage
Span Calibration
Voltage
08
±10 V
0 mV
+10 V
09
±5 V
0 mV
+5 V
0A
±1 V
0 mV
+1 V
0B
±500 mV
0 mV
+500 mV
0C
±150 mV
0 mV
+150 mV
0D
±20 mA
0 mA
+20 mA