2 summary of command set, Command set of analog input modules – ADLINK ND-6017 User Manual

Page 41

Advertising
background image

Command Set

33

Note: 1. There is no spacing between the command words and

The checksum characters.

2. Every command follows a <CR> carriage return for

ending.

3. The checksum characters are optional.

Response of NuDAM Commands

The response message depends on versatile NuDAM command. The
response is composed with a few characteristics, including leading
code, variables, and carriage return for ending. There are two
categories of leading code for response message, ”!“ or ”>“ means valid
command and ”?“ means invalid. By checking the response message,
user can monitor the command is valid or not.

Note: Under the following conditions, there will have no response

message.

1. The specified address ID is not exist.

2. Syntax error.

3. Communication error.

4. Some special commands do not have response.

3.2 Summary of Command Set

There are three categories of NuDAM commands. The first is the
general commands, including set configuration command, read
configuration, reset, read module‘s name or firmware version, etc.
Every NuDAM can response to the general commands. The second is
the functional commands, which depends on functions of each
module. Not every module can execute all function commands. The
third is the special commands including functions about the
programmable watchdog timer, safe values, and the programmable
leading code. All the commands used in the NuDAM analog input
module are list in the following table.

Command Set of Analog Input Modules

Command Syntax

Module

s

Page

General Commands

Set Configuration

%(OldAddr)(NewAddr)
(InputRange)(BaudRate)
(DataFormat)

ALL 3-7

Read Configuration

$(Addr)2

ALL 3-11

Read Module Name

$(Addr)M

ALL 3-12

Advertising