2 summary of command set, Command set of analog input modules – ADLINK ND-6017 User Manual
Page 41
 
Command Set
• 33
Note: 1. There is no spacing between the command words and 
 
The checksum characters.
2. Every command follows a <CR> carriage return for
ending.
3. The checksum characters are optional.
Response of NuDAM Commands
The response message depends on versatile NuDAM command. The 
response is composed with a few characteristics, including leading 
code, variables, and carriage return for ending. There are two 
categories of leading code for response message, ”!“ or ”>“ means valid 
command and ”?“ means invalid. By checking the response message, 
user can monitor the command is valid or not. 
 
Note: Under the following conditions, there will have no response
message.
1. The specified address ID is not exist.
2. Syntax error.
3. Communication error.
4. Some special commands do not have response.
3.2 Summary of Command Set
There are three categories of NuDAM commands. The first is the 
general commands, including set configuration command, read 
configuration, reset, read module‘s name or firmware version, etc. 
Every NuDAM can response to the general commands. The second is 
the functional commands, which depends on functions of each 
module. Not every module can execute all function commands. The 
third is the special commands including functions about the 
programmable watchdog timer, safe values, and the programmable 
leading code. All the commands used in the NuDAM analog input 
module are list in the following table. 
Command Set of Analog Input Modules
Command Syntax
Module
s
Page
General Commands
Set Configuration
%(OldAddr)(NewAddr) 
(InputRange)(BaudRate) 
(DataFormat) 
ALL 3-7
Read Configuration
$(Addr)2
ALL 3-11
Read Module Name
$(Addr)M
ALL 3-12