43 read host watchdog timer & safety value – ADLINK ND-6017 User Manual
Page 92
 
84
• Command Set
3.43 Read Host Watchdog Timer & Safety Value
@Description
Read host watchdog timer setting and the safety value.
@Syntax
~(Addr)3<CR
> 
~
Command leading code.
(Addr)
Address ID
3
Read host watchdog setting and module safety state 
value. 
@Response
!(Addr) (Flag)(TimeOut)(SafeValue)<CR>
 or 
?(Addr)<CR
> 
 
!
Command is invalid.
?
Command is invalid.
(Addr)
Address ID, range (00 - FF).
(Flag)
0: Host watchdog timer is disable 
1: Host watchdog timer is enable(1-character) 
(TimeOut)
Host timeout value. 
Range 01 - FF. (2-character) 
One unit is 100 ms 
01 = 1 * 100 = 100 ms 
FF = 255 * 100 = 25.5 sec 
(SafeValue)
2 channels safety state digital output value when 
host is failure. (2-character) 
@Example
User command:
~063<CR>
Response:
!0611203<CR>
06
Address ID
1
Host watchdog timer is enable.
12
Timeout value. 0x12 = 18 
18 * 100 = 1800 ms 
03
03 (00000011) The safety status of the two digital 
output channels are high. 
(6011/D, 6012/D, 6013
6014D, 6017, 6018)