42 set host watchdog timer & safety value – ADLINK ND-6017 User Manual

Page 90

Advertising
background image

82

Command Set

3.42 Set Host Watchdog Timer & Safety Value

@Description

Set host watchdog timer, module will change to safety state when host
is failure. Define the output value in this command.

@Syntax

~(Addr)2(Flag)(TimeOut)(SafeValue)<CR>

~

Command leading code.

(Addr)

Address ID, range (00 - FF).

2

Set host watchdog timer and safe state value.

(Flag)

0: Disable host watchdog timer
1: Enable host watchdog timer (1-character)

(TimeOut)

Host timeout value, between this time period host
must send (Host is OK) command to module,
otherwise module will change to safety state.
Range 01 - FF. (2-character)
One unit is 100 ms
01 = 1 * 100 = 100 ms
FF = 255 * 100 = 25.5 sec

(SafeValue)

2 channels safety value of digital output channels
when host is failure. (2-character)

@Response

!(Addr)<CR
>
or
?(Addr)<CR
>

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID

(6011/D, 6012/D, 6013

6014D, 6017, 6018)