3 install a new nudam to a existing network – ADLINK ND-6017 User Manual

Page 33

Advertising
background image

Initialization & Installation

25

Initialization Wiring
















Figure 2-1 Layout for Initialization the NuDAM module

2.3 Install a New NuDAM to a Existing Network

Equipments for Install a New Module

A existing NuDAM network

New NuDAM modules

Power supply (+10 to +30 V

DC

)

Installing Procedures

1. Configure the new NuDAM module according to the initialization

procedures in section 2.2.

2. The baud rate and check-sum status of the new module must be

identity with the existing RS-485 network. The address ID must not
be conflict with other NuDAM modules on the network.

3. Power off the NuDAM power supply of the existing RS-485

network.

4. Power off the host computer.
5. Wire the power lines for the new NuDAM with the existing network.

Be careful about the signal polarity as wiring.

6. Wire the RS-485 data lines for the new NuDAM with the existing

network. Be careful about the signal polarity as wiring.

7. Wire to the input or output devices. Refer to section 2.4 for

illustrations.

8. Power on the host computer.
9. Power on the NuDAM local power supply.
10. Use the NuDAM administration utility to check entire network.

Host

Computer


DATA +
DATA -


DATA+
DATA -

Default*

Local Power Supply

+10 V to +30 V

New
NuDAM
module

NuDAM-6520
RS-232/RS-485
Converter

RS-232

+Vs GND

+Vs GND

+Vs GND

Advertising