32 read digital i/o and alarm status – ADLINK ND-6017 User Manual
Page 77
 
Command Set
• 69
3.32 Read Digital I/O and Alarm Status
@Description
Read the digital input channel, digital output channel and the alarm 
state at specified analog input module. 
@Syntax
@(Addr)DI<CR> 
 
@
Command leading code.
(Addr)
Address ID
DI
Read digital I/O and alarm state.
@Response
!(Addr)(Alarm)(DigitalO)(DigitalI)<CR>
!
Command is invalid.
(Addr)
Address ID.
(Alarm)
0: alarm is disable 
1: MOMENTARY mode enable. 
2: LATCH mode enable. 
(1-character) 
(DigitalO)
Digital output channel, port 0 and 1 status. 
00: channel 0 is OFF, channel 1 is OFF 
01: channel 0 is ON , channel 1 is OFF 
02: channel 0 is OFF, channel 1 is ON 
03: channel 0 is ON , channel 1 is ON 
(2-character) 
(DigitalI)
Digital input channel, port status. 
00: channel is LOW. 
01: channel is HIGH. 
(2-character) 
(6011/D, 6012/D, 6014D)