Command Set

@Example

User command:

@06DI<CR>

Response:

!0620301<CR>

Item Meaning

Description

!

(Leading Code)

Command leading code.

06

(Addr)

Analog module’s address ID is 06H.

2

(Alarm)

2 means alarm state is LATCH.

03

(DigitalO)

Digital output channel status.
03: channel 0 is ON
channel 1 is ON

01

(DigitalI)

Digital input channel status
01: digital input is HIGH.


Read digital I/O and alarm at address 06H. alarm state is LATCH, digital
output channel port 0 and 1 are ON and digital input channel is HIGH.