• 3

C: 0

°C~2320°C

•

Voltage Range: Programmable 6 levels

±2.5V, ±1V, ±500mV, ±100mV, ±50mV, ±15mV

• Current

Measurement:

±20mA (with external 125Ω resistor)

• Accuracy:

±0.4%

Note

(1)

: F/W version above A4.60 support K-type for 0~1370

°

C. Lower version

supports K-type for 0~1000

°

C.

—

Digital Output

•

Channel numbers: 2

•

Output characteristic: open collector transistor

•

Maximum current sink: 50mA

•

Max. power dissipation: 300mW

—

Digital Input

•

Channel numbers: 1

•

Logical level 0: +1V maximum

•

Logical level 1: +2.0V~ +30V

•

Pull up resister: 10K

Ω

•

Maximum current: 0.5mA

—

Watchdog Function

•

Module internal watchdog timer: 150 ms

•

Power failure threshold: 4.65 V

•

Safety value: 2 digital output channels

•

Host programmable watchdog: 100 ms ~ 25.500 sec

—

Power

•

Power supply: +10V to +30V

•

Current consumption: 0.76W(1.68W for NuDAM-6011/D)