23 read target high/low values for linear mapping – ADLINK ND-6017 User Manual
Page 68
 
60
• Command Set
3.23 Read Target High/Low Values for Linear
Mapping
@Description
Read the mapped high/low limit values from input for linear mapping.
@Syntax
$(Addr)5<CR>
$
Command leading code.
(Addr)
Address ID
5
Read the mapped high/low limit values from input for 
linear mapping . 
@Response
!(Addr)(Data_L)(Data_H)<CR> 
 or 
?(Addr)<CR> 
 
!
Command is invalid.
(Addr)
Address ID.
(Data_L)
Mapped low limit value for linear mapping. 
Data format is with an + or - sign with five decimal 
digits and a decimal fixed point. 
(Data_H)
Mapped high limit value for linear mapping. 
Data format is with an + or - sign with five decimal 
digits and a decimal fixed point. 
?
Command is invalid.
@Example
User command:
$055<CR>
Response:
!05-20.000+20.000<CR>
 
The module is configured for +20~-20mA input current range. The linear 
mapping function had been executed. This command is to read the 
mapped high/low values for linear mapping. The mapped high limit 
value is +20mA and mapped low limit value is -20mA. The address of 
this module is 05H. 
(6014D)