24 write source high/low values for linear mapping – ADLINK ND-6017 User Manual

Page 69

Advertising
background image

Command Set

61

3.24 Write Source High/Low Values for Linear

Mapping

@Description

Write the source high/low limit values from input for linear mapping.

@Syntax

$(Addr)6(Data_L)(Data_H)<CR>

$

Command leading code.

(Addr)

Address ID

6

Set the high/low limit values from input for linear
mapping .

(Data_L)

Low limit input value for linear mapping. It must be lower
than the high limit input value. The format of data is the
same as input current range. The minimum input value
could equal to the minimum input value of input current
range. Data format is with an + or - sign with five decimal
digits and a decimal fixed point.

(Data_H)

High limit input value for linear mapping. It must be higher
than the low limit input value. The format of data is the
same as input current range. The maximum input value
could equal to the maximum input value of input current
range. Data format is with an + or - sign with five decimal
digits and a decimal fixed point.

@Response

!(Addr)<CR>
or
?(Addr)<CR>

!

Command is invalid.

(Addr)

Address ID.

?

Command is invalid.

@Example

User command:

$036-100.00+100.00<CR>

Response:

!03<CR>


The module is configured for +150~-150mV input range. This command
is to set the input high/low values from +100.00 to –100.00mV for
linear mapping. The address of this module is 05H.

(6014D)