25 write target high/low values for linear mapping – ADLINK ND-6017 User Manual

Page 70

Advertising
background image

62

Command Set

3.25 Write Target High/Low Values for Linear

Mapping

@Description

Write the target high/low limit values from input for linear mapping.

@Syntax

$(Addr)7(Data_L)(Data_H)<CR>

$

Command leading code.

(Addr)

Address ID

7

Set the mapped high/low limit values from input for
linear mapping .

(Data_L)

Mapped low limit input value for linear mapping. It
must be lower than the mapped high limit input
value. Data format is with an + or - sign with five
decimal digits and a decimal fixed point.

(Data_H)

Mapped high limit input value for linear mapping. It
must be Higher than mapped the low limit input
value. Data format is with an + or - sign with five
decimal digits and a decimal fixed point.

@Response

!(Addr)<CR>
or
?(Addr)<CR>

!

Command is invalid.

(Addr)

Address ID.

?

Command is invalid.

@Example

User command:

$036-100.00+100.00<CR>

Response:

!03<CR>


The module is configured for +150~-150mV input range. This command
is to set the input high/low values from +100.00 to –100.00mV for
linear mapping. The address of this module is 03H.