ADLINK ND-6017 User Manual

Page 14

Advertising
background image

6

Introduction

1.3 Overview

of

NuDAM-6012/D

What is NuDAM-6012/D?

NuDAM-6012/D is a multi-functions analog input module. The
programmable input voltage range of analog input channel is from

±10V

maximum to

±150mV minimum.

The module also provides the alarm function and the event counter just
like NuDAM-6011/D. In fact, the NuDAM-6012/D provides almost all
functions that NuDAM-6011/D has except the CJC and temperature
measurement function.

Features of NuDAM-6012/D

1 analog input channel with differential input

Programmable voltage range

5000 Vrms isolation voltage for AD channel (2500 Vrms for
ND-6012/D)

2 digital output channels of open collector type

Alarm function with high / low alarm output

1 digital input channel / event counter

Programmable host watchdog timer for host failure protection

Internal watchdog timer for device failure protection

Easy programming by software

Easy installation and wiring

51/2 digital LED display (NuDAM-6012/D)

Specifications of NuDAM-6012/D

—

Interface

Interface: RS-485, 2 wires

Speed (bps): 1200, 2400, 4800, 9600, 19.2K, 38.4K ,115.2K
(115.2K only for firmware reversion above A4.00)

—

Analog Input

Input type: Differential input

Resolution: 16 bits

Unit Convertion: mV, V, or mA

Voltage Range: Programmable 5 levels

±10V, ±5V, ±1V, ±500mV, ±150mV

• Current

Measurement:

±20mA (with external 125Ω resistor)

• Accuracy:

±0.05%

Isolation Voltage: 5000 Vrms(2500 Vrms for NuDAM-6012/D)