Figure 18 – CIRCUTOR AFQ Series User Manual

Page 24

Advertising
background image

AFQ-4W

24 Instruction Manual

Figure 18: Transformer connection points in the AFQ-4W.

Class 0.2S transformers of the CT or TCH series are recommended.

The use of class 0.2, 0.5s or 0.5 transformers will slightly jeopardise the

behaviour of the active filter although they always provide acceptable harmonic

filtering replies.

The use of transformers with ratios close to the current to be

measured is recommended.

Current transformers TI1, TI2, TI3 must be correctly connected for the

AFQ-4W filters to work properly. If the phases L1, L2 and L3 are

switched in the secondary, the filter will not work properly.

Check the connections and make sure that:

TI1 measures phase 1 and the transformer output cables are

connected in posts S1/L1 and S2/ L1 of the filter cabinet.

TI2 measures phase 2 and the transformer output cables are

connected in posts S1/L2 and S2/ L2 of the filter cabinet.

TI3 measures phase 3 and the transformer output cables are

connected in posts S1/L3 and S2/ L3 of the filter cabinet.