Standard, Maintenance – CIRCUTOR AFQ Series User Manual

Page 64

Advertising
background image

AFQ-4W

64 Instruction Manual

5.1. STANDARD MAINTENANCE

Perform maintenance in 6 to 12 monthly intervals, depending on the

environmental dirt and operation of the unit.

The points to be followed are:

1.- Set the AFQ-4W in STOP mode and turn off the main switch

(OFF position).

2.- Wait 5 minutes for the capacitors to discharge.

3.- Clean the ventilation grilles, the inside of the unit and fans.

4.- Check the state and tightness of the electrical connections.

5.- Replace the display battery if necessary.

The display uses a CR2032 3V battery. The LED in the bottom left corner of the

display indicates the state of the battery.

Green: the battery is correct.
Red: low battery level.

Figure 64: Rear of the display.

The battery display is in its rear, as indicated in

Figure 64

.

It is best to note the configuration of the AFQ-4W,

refer to 4.3.-

CONFIGURACIÓN

.

When the panel battery is changed, the language, date and time of the unit have

to be reconfigured. (refer to

4.3.5.- SCREEN CONFIGURATION).

Display battery

Advertising