APPENDIX A: DISPLAY MESSAGES

The tables below show all of the messages that might appear on the main

screen, along with the description and the corresponding corrective action.

Disconnect the main switch before starting any maintenance task on

the AFQ-4W filters. After the main switch has been disconnected,

wait at least 5 minutes to ensure that all the DC side capacitors and

the parallel passive filter are completely discharged.

ACTIVE FILTER STOPPED

Table 12

shows the messages that might appear on the main screen before the

AFQ-4W starts up.

NOT INITIAL CONDITIONS (Initial conditions not met)

Starting ...

Description

AFQ-4W is starting

Corrective

Action

Wait until the initialisation is complete.
If the message is still displayed, check the RS-232
communications cable between the panel and the controller board.

Set Up transformer ratio

Description

The transformation ratio of the load measuring transformer is not
configured.

Corrective

Action

Check section 4.3.3.- CONFIGURATION OF PARAMETERS

to configure the transformer ratio.

MIN. Load current

Description

The load current is below the minimum limit programmed in the
AFQ-4W.

Corrective

Action

The minimum current of the AFQ-4W can be changed in section

4.3.3.- CONFIGURATION OF PARAMETERS

Mains voltage fault.

Description

Mains voltage too low.

Corrective

Action

Check the input voltage of the three phases of the AFQ-4W and
the circuit breaker 1Q22.