Table 12 – CIRCUTOR AFQ Series User Manual

Page 92

Advertising
background image

AFQ-4W

92 Instruction Manual

MIN. DC bus voltage

Description

The DC bus voltage is too low.

Corrective

Action

Check the input voltage of the three phases of the AFQ-4W and
the circuit breaker 1Q22.

Synchronising

Description

Synchronising with the mains frequency.

Corrective

Action

Check the input voltage and the connections if the message
remains on the screen.

Polarity Error

Description

Error measuring the load current.

Corrective

Action

Check the measuring transformers connection. Check the unit
configuration, 4.3.2.- OPERATION MODE CONFIGURATION.

DC Bus imbalance

Description

The capacitor voltage is decompensated.

Corrective

Action

Reduce the number of harmonics to be neutralised.

NTC connector failure

Description

The NTC temperature probe is disconnected or the temperature
inside the unit is below 0ºC.

Corrective

Action

Make sure the NTC probe is connected to the controller board.
If the temperature inside the cabinet is under 0ºC, do not start the
unit.

Table 12: Not Initial Conditions messages.