CIRCUTOR AFQ Series User Manual

Page 56

Advertising
background image

AFQ-4W

56 Instruction Manual

Do not use the Temporary mode (2) if the supplier has not

recommended this for their installation. This method can cause

resonance in certain installations.

Power limit

This parameter allows the maximum power of the active filter to be limited. The

value is configured as a percentage with respect to the unit's nominal power. The

minimum configurable value is 20%, and the maximum is 100%.

Parallel Modules :

Access to the configuration screen of the number of active filters set out in

parallel with the same load (

Figure 57

).

Figure 57: Parallel module configuration screen.

A maximum of 8 AFQ-4W units can be installed in parallel, with different power

ratings.

All of the AFQ-4W must use the same load transformer. Refer to the

section

3.6.- PARALLEL CONNECTION OF 2 TO 8 ACTIVE FILTERS

to install more than one active filter in parallel.