5.- MAINTENANCE

The AFQ-4W active filter requires a minimum of preventive maintenance.

It is recommended to follow the notes described in this chapter to

avoid premature damage to the unit's components.

Table 10

shows the maintenance jobs with their respective time intervals.

Description

Interval

Standard maintenance

5,000 to 9,000 hours

Cooling turbines (for AFQ-4W-100, AFQ-4W-150 and AFQ-4W-
200
)

40,000 h

Cooling fans

100,000 h

DC bus capacitors

200,000 h

Table 10: Active filter maintenance.

Note: The time intervals of the maintenance operations can vary depending on

the unit's operating conditions and environmental factors.

Follow the safety instructions given in “SAFETY PRECAUTIONS

before any maintenance operation in the AFQ-4W filters.

Failure to follow these instructions may result in injury or even

death.

Certain components in the unit can reach high temperatures.

Allow the unit to cool down before performing any maintenance

operations.