Enable alarm – CIRCUTOR AFQ Series User Manual

Page 53

Advertising
background image

AFQ-4W

Instruction Manual 53

4.3.2.3.- ENABLE ALARM

This screen (

Figure 55

) allows us to control the different alarms:

Figure 55: Alarm activation screen.

Polarity alarm:

With the polarity alarm enabled, the active filter detects the direction of the load

measuring transformer current and if it detects inverse polarity (current towards

the mains) it returns to the initial conditions and restarts with the new conditions

in measuring the current. In the case of regenerative loads temporarily injecting

current into the mains, the polarity alarm will be activated.

With the polarity alarm disabled, if the load is injecting energy into the mains,

the AFQ-4W will measure negative active power and will stop neutralising

harmonics, balancing phases and compensating reactive energy. It will only

adjust the bus to the operating voltage.

When the active power is positive again, it will reperform all of the filtering

functions.

Disable the polarity alarm only in installations with loads temporarily

injecting current into the mains.

This option is enabled by default and it is recommended not to

disable it.

Before starting the active filter with the polarity alarm disabled, check

the connection and polarity of the load measuring transformers.