B.2.2 single/multiple fan failure, Table b-5, Airflow summary for a single/multiple fan failure – Artesyn Centellis 2000 Shelf - DC Installation and Use (June 2014) User Manual

Page 165: Table b-6, Quadrant detail for a single/multiple fan failure, Technical data

Advertising
background image

Technical Data

Centellis 2000 Shelf - DC Installation and Use (6806800G45F)

165

B.2.2

Single/Multiple Fan Failure

Airflow data for the front left failure condition is worse than for any other single fan failure, and
that data is presented in this section.

Table B-5 Airflow Summary for a Single/Multiple Fan Failure

Chassis

Front Blade (FB)

RTM

Total

84.5 CFM

70.2 CFM

14.3 CFM

Maximum

-

35.2 CFM

7.5 CFM

Minimum

-

35.1 CFM

6.8 CFM

Average

-

35.1 CFM

7.2 CFM

Table B-6 Quadrant Detail for a Single/Multiple Fan Failure

FBQ1

FBQ2

FBQ3

FBQ4

FB Total

RTM

Slot 1

9.0 CFM

8.8 CFM

8.5 CFM

8.9 CFM

35.2 CFM

6.8 CFM

Slot 2

8.8 CFM

8.7 CFM

7.9 CFM

9.6 CFM

35.1 CFM

7.5 CFM