Table b-9, Airflow summary during rear fan tray replacement, Table b-10 – Artesyn Centellis 2000 Shelf - DC Installation and Use (June 2014) User Manual

Page 168: Quadrant detail during rear fan tray replacement, Figure b-7, Technical data

Advertising
background image

Technical Data

Centellis 2000 Shelf - DC Installation and Use (6806800G45F)

168

Figure B-7

RTM Slot Volumetric Flow during Front Fan Tray Replacement

Table B-9 Airflow Summary during Rear Fan Tray Replacement

Chassis

Front Blade (FB)

RTM

Total

91.5 CFM

79.9 CFM

11.6 CFM

Maximum

-

40.5 CFM

5.9 CFM

Minimum

-

39.4 CFM

5.7 CFM

Average

-

39.9 CFM

5.8 CFM

Table B-10 Quadrant Detail during Rear Fan Tray Replacement

FBQ1

FBQ2

FBQ3

FBQ4

FB Total

RTM

Slot 1

10.1 CFM

9.8 CFM

9.2 CFM

10.2 CFM

39.4 CFM

5.7 CFM

Slot 2

10.7 CFM

9.3 CFM

10.0 CFM

10.6 CFM

40.5 CFM

5.9 CFM