66

The environmental values must be tested and proven in the planned system configuration,
that is, the delivered system and other third-party products you want to integrate.

The following table lists the environmental requirements.

Operating temperatures refer to the temperature of the air circulating at the air intake of
the system and not to component temperatures.

Some of the climatic values may exceed the specification of some system components
(for example, hard disks). As Artesyn Embedded Technologies cannot guarantee the
functionality of third party products that are handled or operated out of their
specifications, the environmental conditions may be limited to the specifications of
these components.

Table 2-1 Environmental Conditions

Feature

Operating

Non-Operating (packed state)

Temperature

+5 ºC (41 °F) to +40 ºC (104 °F)
(normal operation) according to NEBS
standard GR-63-CORE
-5 °C (23 °F) to +55 °C (131 °F)
(exceptional operation) according to NEBS
standard GR-63-CORE

-40 °C (-40 °F) to +70 °C (158 °F)

Temp. change

+/-0.5 °C/min according to NEBS standard
GR-63-CORE

+/-0.5 °C/min

Relative
humidity

5% to 90% non-condensing
according to Artesyn Embedded
Technologies-internal environmental
requirements

5% to 95% non-condensing
according to Artesyn Embedded
Technologies-internal environmental
requirements

Vibration
(tested in
target
platform)

0.1 g from 5 to 100 Hz and back to 5 Hz at
a rate of 0.1 octave/minute

5-20 Hz at 0.01 g

2

/Hz

20-200 Hz at -3.0 dB/octave
Random 5-20 Hz at 1m

2

/Sec

3

Random 20-200 Hz at -3 dB/octave

Shock

Half-sine, 11 mSec, 30 m/Sec

2

Blade level packaging
Half-sine, 6 mSec at 180 m/Sec

2