System Installation

Centellis 2000 Shelf - DC Installation and Use (6806800G45F)

75

Observe the following general safety notes when installing your system:

Restricted access area: Install the system only in a restricted access area.

Installation codes: This unit must be installed in accordance with the National Electrical
Code, Articles 110-16, 110-17, and 110-18 and the Canadian Electrical Code, Section
12.

Conductor ampacity - According to UL 60950, Annex NAE (NEC Article 645-5(a)), the
branch-circuit conductors supply must have an ampacity of not less than 125% of the
total connected load. Per NEC Article 310-15 and Table 310-16, the minimum
American Wire Gauge (AWG) has to be selected.

Overcurrent protection: A readily accessible listed branch circuit overcurrent protective
device must be incorporated into the building wiring. For appropriate AWG rating of
the overcurrent protection device see NEC Table 310.16 and other national regulations.
The circuit interrupter of the overcurrent protective device must be rated at 315 A
maximum.

Artesyn Embedded Technologies is not responsible for regulatory compliance or malfunction
of any user-modified product.