3 installation / operation tasks, Operator interface – Flowserve 400MD Logix User Manual

Page 14

Advertising
background image

Table 2.1 Components Required for Logix 3400MD Digital Positioner Installation

Components

Description

Logix3400MDDigitalPositioner

Fieldbus positioner.

Power supply

Furnishes DC power to fieldbus devices.

Power conditioner

Acts as a filter to prevent the power supply from interfering with the fieldbus signaling. (May be part

of a fieldbus power supply.)

Fieldbus cable

Twisted pair shielded wire used to interconnect fieldbus devices.

Fieldbus terminators

Fieldbus IS Barriers (For hazardous area installations)

A signal termination device used to prevent reflected signals (noise) from distorting fieldbus

communications.

Intrinsic safety wire barriers are required for hazardous location installations.

Fieldbus wiring blocks

Wiring blocks allowing easy connection of devices, cable, terminators, surge suppressors and other

fieldbus network components.

Operator Interface

In the control room an operator station, a personal computer or host computer acts as the operator interface to the fieldbus network. Using
supervisory control software applications, the field devices on a fieldbus network can be monitored and controlled at the operator interface.
Figure 2.1 shows how these components go together to operate on a fieldbus network.

Figure 2.1 Fieldbus Network Components

2.3 Installation / Operation Tasks

Installation of the Logix 3400MD digital positioner is not difficult. The tasks for installing and operating the Logix 3400MD digital positioner
are outlined in Table 2.2.

Power

Supply

PC

T

T

Operator Station or

Host Computer

Fieldbus Cable

Fieldbus Device

T

= Terminator

PC

= Power Conditioner

Logix 3400MD Digital Positioner LGENIM3405-02 11/13

14